Two Minnesota sprinkler fitters: FIELD, a beat-up old journeyman who's hung more pipe than you've walked past, and CODE, a cocky apprentice who's read the book twice and thinks that makes him dangerous. Raw, 18+ late-night talk on the MN Journeyman Sprinkler Fitter exam, built on the MSFC, NFPA 13, 14 and 25 and Minnesota rules, checked against the text, not barstool lore.
Made by fitters who still work the job, for the brothers and sisters trying to get that card. Pair it with the MN Journeyman Exam Prep app. New episodes every day.
Made by fitters who still work the job, for the brothers and sisters trying to get that card. Pair it with the MN Journeyman Exam Prep app. New episodes every day.
193 Episodes
Reverse
Control valves: listed indicating valves, PIVs and wall PIVs, check valves, and the four ways to supervise a valve. We cover valve location and accessibility, no shutoff in the FDC line, valves on both sides of a check, PRVs at 175/165 psi with the half-inch relief, PIV height of 32 to 40 inches above grade, floor control assemblies, Minnesota's locked-open valve security rule, and NFPA 25 valve ITM.Two fitters, a lot of swearing (18+), a lightning round, and a war story about a tagged valve, a hidden second feed, and a face full of water. Numbers are from NFPA 13-2019 with 2016 section numbers where Minnesota still points (Minn. R. 7511.8000), plus Minnesota amendments in Minn. R. 7511.0903. Check the edition your exam uses. NFPA 25-2020 for ITM.App news: Minnesota Journeyman Exam Prep is available now on Google Play (Android only). Thanks to our closed testers. Link below.Google Play: https://play.google.com/store/apps/details?id=com.mnfireexamprep.app
The Hazen-Williams formula in plain English, the C-factor table (100, 120, 140, 150), why the fitting table is "C = 120 only" and how the multipliers work, equivalent lengths for elbows, tees, and valves, what's in and out of the calc, feet of head vs. psi, and K = Q/√P with worked examples. Minnesota adopts NFPA 13-2016 (Hazen-Williams is 23.4.2.1.1 there), and we flag it.Plus a war story about one branch line, eight extra elbows, and a remote area that came up short.Explicit language. 18+ only.Testers group: https://groups.google.com/g/mn-journeyman-exam-testersAndroid app testing: https://play.google.com/apps/testing/com.mnfireexamprep.app
Class I through IV, Group A/B/C plastics, cartoned vs. exposed, the 5/15 and 5/25/40 percentage rules, plastic pallets, open vs. closed arrays, rack types, flues, mixed commodities, and the general information sign. Minnesota adopts NFPA 13-2016, so we flag the 2016 numbers alongside 2019.Plus a mattress-warehouse war story about what happens when the stuff in the boxes changes and nobody reads the sign.Explicit language. 18+ only.Testers group: https://groups.google.com/g/mn-journeyman-exam-testersAndroid app testing: https://play.google.com/apps/testing/com.mnfireexamprep.app
Is there enough water, for long enough? At least one automatic supply, what counts as a supply, the 6-inch private main rule, pressure tanks, a live two-hydrant flow test (static, residual, measure the outlet), 0.433 psi per foot and 2.31 feet per psi, then the two evil-twin tables: hydraulically calculated hose stream and duration (100/250/500 gpm; 30, 60-90, 90-120 min) vs. pipe schedule (15 or 20 psi at the top, flows that already include hose). Inside vs. outside hose, where each gets added, monitored-system lower durations, mixed hazards, minimum design areas, tank math, and the hydraulic sign.Two fitters, a lot of swearing (18+), a lightning round, and a war story about an eleven-year-old flow test and a water park that stole the water. Numbers from NFPA 13-2019 with 2016 numbers where Minnesota still points (Minn. R. 7511.8000). Check your exam's edition.App news: the MN Journeyman Exam Prep Android app has enough testers and the 14-day Google Play countdown has started. It should go public in a couple of weeks once Google reviews it. Thanks, testers. We'll tell you the minute it's live.Google Group: https://groups.google.com/g/mn-journeyman-exam-testersPlay testing: https://play.google.com/apps/testing/com.mnfireexamprep.app
The plain-Jane system nobody studies. How an alarm check valve and retard chamber actually work (and why a plugged retard drain makes the outside bell ring like a drunk church), gauges above and below the check, the relief valve "175 psi or 10 over, whichever is greater," the more-than-20-sprinklers local alarm, 3/8-inch vs. 3/4-inch alarm piping, the 3/4-inch strainer, alarm bypass test connections, paddle switches (wet only), and the wet inspector's test connection: 1 inch, smooth bore, smallest K-factor or less, anywhere downstream of the flow device, alarm within 5 minutes.Two fitters, a lot of swearing (18+), a riser-room troubleshooting round, a lightning round, and a nursing-home war story about a booster pump, a 2 a.m. gong and a fire captain with donuts. Sprinkler-side only; the NFPA 72 panel side was its own episode. Numbers from NFPA 13-2019 with 2016 numbers where read (Minn. R. 7511.8000 still points to 2016). Check your exam's edition.App news: the MN Journeyman Exam Prep Android app has enough testers and the 14-day Google Play countdown has started. It should go public in a couple of weeks once Google reviews it. Thanks, testers. We'll tell you the minute it's live.Google Group: https://groups.google.com/g/mn-journeyman-exam-testersPlay testing: https://play.google.com/apps/testing/com.mnfireexamprep.app